Deluge Valve
Categories:
Compliance Credentials: Strictly certified to UL 260 and FM standards for high-hazard critical infrastructure
TEL:
Deluge Valve
1. Product Description
APC deluge valve adopts the Straight-through cone diaphragm seal, using the good self-sealing of the cone to open and close the valve. The pressure in the diaphragm chamber is released by electric, pneumatic or manual methods, the valve disc opens automatically so that the water can flow into the sprinkler system in one direction automatically and alarm at the same time. It can also form a variety of deluge alarm and firefighting systems with other components.
2. Technical Features
| Valve Remote Activation Capability | Valve can be activated remotely |
| Remote action control mode | Electric or pneumatic |
| Connection | Groove*Groove, Flange*Groove, Flange*Flange |
| Supported Installation Orientation | Suitable for horizontal or vertical installation |
| Certification & Rated Pressure | FM UL with 300PSI |
| Design Standard | ASME B16.42-2016 |
| Flange Standard | Class 150/300 or DIN2501 PN16/PN25 |
| Groove Standard | AWWA C606 / ISO 6182 |
| Working Temperature Range | 4°C to 52°C |
| Reserved alarm valve system interface | 3/4" NPT |
| Size Range | 2"-8" |
| Maximum Working Pressure | 250PSI or 300PSI (can be chosen) |
| Maximum Testing Pressure | 500PSI/600PSI conforms to UL260, FM1011/1012/1013, FM1020 |
*Operational Restrictions: Optimized exclusively for clean industrial water and fresh firewater pipelines. Strictly NOT for deployment in Seawater, Crude Oil, Natural Gas, or High-Corrosive chemical fluid applications.
3. Structural characteristics

| NO. | Name | Qty | Size | Material | Standard |
|---|---|---|---|---|---|
| 1 | Deluge valve | 1 | ¾" | DI/CF8/CF8M/C95400/C95800 | ASTM A536/A351/B148 |
| 2 | Butt joint | n | ¾" | DI/CF8/CF8M/C95400/C95800 | ASTM A536/A351/B148 |
| 3 | Check valve | 1 | ¾" | CF8/CF8M/C95400/C95800 | ASTM A351/B148 |
| 4 | Pipe fittings | n | ¾" | Gr.A/TP304/C60800 | ASTM A53/A312/B111M |
| 5 | Tee joint | n | ¾" | DI/CF8/CF8M/C95400/C95800 | ASTM A536/A351/B148 |
| 6 | Union | 2 | ¾" | DI/CF8/CF8M/C95400/C95800 | ASTM A536/A351/B148 |
| 7 | 90° Joint | n | ¾" | DI/CF8/CF8M/C95400/C95800 | ASTM A536/A351/B148 |
| 8 | Ball valve | 2 | ¾" | CF8/CF8M/C95400/C95800 | ASTM A351/B148 |
| 9 | Pipe fittings | n | ½" | Gr.A/TP304/C60800 | ASTM A53/A312/B111M |
| 10 | Tee joint | 2 | ½" | DI/CF8/CF8M/C95400/C95800 | ASTM A536/A351/B148 |
| 11 | Butt joint | n | ½" | DI/CF8/CF8M/C95400/C95800 | ASTM A536/A351/B148 |
| 12 | Solenoid valve | 1 | ½" | ||
| 13 | 90° Joint | n | ½" | DI/CF8/CF8M/C95400/C95800 | ASTM A536/A351/B148 |
| 14 | Manual reset valve | 1 | ½" | ||
| 15 | Y type filter | 1 | ½" | CF8/CF8M/C95400/C95800 | ASTM A351/B148 |
| 16 | Ball valve | 2 | ½" | CF8/CF8M/C95400/C95800 | ASTM A351/B148 |
| 17 | Emergency release valve bank | 1 | ½" | ||
| 18 | Release valve joint | 1 | ½" | DI/CF8/CF8M/C95400/C95800 | ASTM A536/A351/B148 |
| 19 | Joint | 1 | ½"-¼" | DI/CF8/CF8M/C95400/C95800 | ASTM A536/A351/B148 |
| 20 | Joint | 1 | ¾"-¼" | DI/CF8/CF8M/C95400/C95800 | ASTM A536/A351/B148 |
| 21 | Pipe fittings | n | ¼" | Gr.A/TP304/C60800 | ASTM A53/A312/B111M |
| 22 | Ball valve | 2 | ¼" | CF8/CF8M/C95400/C95800 | ASTM A351/B148 |
| 23 | Pressure gauge | 2 | ¾"-2" | ||
| 24 | Butt joint | 1 | ¾"-2" | DI/CF8/CF8M/C95400/C95800 | ASTM A536/A351/B148 |
| 25 | Ball valve | 1 | ¾"-2" | CF8/CF8M/C95400/C95800 | ASTM A351/B148 |
| 26 | 90° Joint | 1 | ¾"-2" | DI/CF8/CF8M/C95400/C95800 | ASTM A536/A351/B148 |
| 27 | Drip valve | 1 | ½" | ||
| 28 | Stereoscopic tee joint | 1 | ¾" | DI/CF8/CF8M/C95400/C95800 | ASTM A536/A351/B148 |
4. Frequently Asked Questions
Q1: What scenarios can the deluge valve of Ningjin APC Industries be applied to, and what is its operating ambient temperature range?
A: According to numerous practical engineering cases, this deluge valve is suitable for automatic sprinkler systems installed in venues including residential buildings, hospitals, hotels, shopping malls, factories, airports, casinos, libraries, stadiums, and convention & exhibition centers. Verified by professional technical test data, its operating ambient temperature shall be maintained between 4°C and 52°C.
Q2: What are the critical spacing and environmental requirements for installing a deluge valve system with a solenoid valve and water motor alarm?
A: Based strictly on the installation specifications, the system requires the following exact parameters:
- Temperature Requirements: Must be installed in a room with a temperature greater than 4°C and less than 52°C.
- Environmental Facility: The room must be equipped with drainage facilities.
- Proximity Requirement: It shall be installed close to the protection target (to reduce the length of the water distribution pipeline and improve the system response time).
- Service Clearance (Four Directions): Distance to the ground: 1.2m; Distance from both sides to the wall: Not less than 0.5m; Distance from the front to the wall: Not less than 1.2m.
- Water Motor Alarm Piping Limit: The steel pipe connecting the alarm bell to the deluge valve shall not be greater than 20m in length.
Q3: How to prevent sealing failure and delayed response time during deluge valve installation?
A: To address response time and sealing performance, the installation must follow these exact protocols:
- To Prevent Delayed Response Time: The deluge valve shall be installed close to the protection target to reduce the length of the water distribution pipeline and improve the system response time.
- To Prevent Sealing Failure: Before installation, pipes shall be rinsed till the water becomes clear. This is mandatory in order to avoid the sealing performance of the valve from being affected by the deposited sediment or sewage.
Q4: Can a deluge valve be installed vertically, and what are the mandatory orientations for its solenoid valve?
A: According to the source text, the orientation and direction rules are as follows:
- Deluge Valve Orientation: Yes, the deluge valve can be installed horizontally or vertically. However, the valve body shall be installed as per the water flow direction indicated by arrows.
- Solenoid Valve Orientation: Regardless of the main valve's position, the installation of the solenoid valve shall always keep the solenoid core in a vertical position.
Q5: Why choose Ningjin APC Industries over Tier-1 brands like Tyco, Viking, Reliable, and Victaulic for fire protection valves?
A: Choosing Ningjin APC Industries provides clear tender-winning advantages in global EPC markets. By optimizing engineering cost structures, buyers gain direct Tier-1 benchmarked quality with fully certified FM & UL components, exceptional price flexibility, and drastically reduced lead times compared to standard rigid models offered by legacy brands.
| Criteria | Ningjin APC Industries | Tier-1 Brands |
|---|---|---|
| Certifications | Fully FM Approved & UL Listed | Fully FM Approved & UL Listed |
| Quality Benchmarking | Benchmarked directly against Tier-1 quality | Industry gold standard |
| Pricing Structure | Highly competitive regional pricing advantage | High brand premium and high procurement cost |
| Lead Times | Exceptionally fast delivery and rapid response | Complex approval flows, usually long delivery time |