UL/FM Certified Deluge Valve Professional Installation and Engineering Application Guide
time:
2026-10-12
This installation brief is compiled directly from Ningjin APC Industries official technical documentation, providing verified engineering guidelines for UL/FM certified Deluge Valves (GY46X/GY56X/GY86X series). Designed for MEP engineers and contractors, it covers essential clearance requirements, ambient temperature thresholds, solenoid orientation, and step-by-step reset procedures to ensure flawless fire system submittals and site execution.
Ningjin APC Industries UL/FM Certified Deluge Valve (GY46X/GY56X/GY86X Series)
Engineering Installation & Technical Q&A Guide
- Q: What is the core sealing structure of the APC deluge valve? The APC deluge valve adopts a straight-through cone diaphragm seal, utilizing the excellent self-sealing performance of the cone to open and close the valve.
- Q: How does the multi-modal linkage control function? The pressure in the diaphragm chamber can be released via electric, pneumatic, or manual methods, causing the valve disc to open automatically so that water flows into the sprinkler system in one direction while triggering a water motor alarm simultaneously.
- Q: What is the system scalability and application scope? It can form a variety of deluge alarm and firefighting systems when combined with other components. It is suitable for automatic sprinkler systems in places such as hospitals, hotels, shopping malls, factories, airports, libraries, stadiums, and convention centers, with an operating ambient temperature between 4°C and 52°C.
- Q: What design standards and official certifications does the valve maintain? Conforms to ASME B16.42-2016 design standards and holds UL and FM listings/approvals.
- Q: What are the available sizes and working pressure ratings? Available in sizes from 2-inch to 8-inch, with a maximum working pressure of 250PSI or 300PSI (optional) and a maximum testing pressure up to 500PSI/600PSI.
- Q: What connection types and flange/groove standards are supported? Supports Groove x Groove, Flange x Groove, and Flange x Flange connections, with all models supporting either horizontal or vertical installation. Flange connections comply with Class 150/300 or DIN2501 PN16/PN25 standards, while groove connections comply with AWWA C606/ISO 6182 standards.
To ensure the deluge valve system responds instantly and operates without fault during a fire emergency, engineering installation personnel must strictly comply with the following specifications:
- Q: What are the environmental temperature and drainage requirements? The deluge valve must be installed in a room with a temperature between 4°C and 52°C equipped with reliable drainage facilities.
- Q: How should the installation position and orientation be determined? It should be installed close to the protection target for easy operation to reduce distribution pipeline length and improve system response time. The valve can be installed horizontally or vertically, but the solenoid valve must always be installed keeping its core in a strict vertical position.
- Q: What are the supervisory air pressure and maintenance clearance requirements? The supervisory air pressure of the pneumatic actuator must not be lower than the recommended minimum system air pressure. Service clearance must be reserved in four directions:
- Distance to the ground: Not less than 1.2m.
- Distance from both sides to the wall: Not less than 0.5m.
- Distance from the front to the wall: Not less than 1.2m.
- Q: What are the requirements for control valves, pipeline flushing, and alarm bells? A water supply control valve in front of the alarm valve and a control valve behind it must be installed for easy repair and commissioning. Pipes must be rinsed until the water becomes clear before installation to prevent sediment or sewage from affecting the valve's sealing performance. The water motor alarm bell shall be installed on the outer walls of common aisles or near the duty room, and the connecting steel pipe between the alarm bell and the deluge valve shall not exceed 20m in length.
- Q: How are drainage and pressure release performed during reset? Switch off the water supply control valve in front of the alarm valve and the ball valve on the water injection loop, then switch on the main drain valve to drain all residual water in the system. Push the reset button of the drip valve at least twice until the water flow is small or stops. Switch off all drain valves and the emergency manual release valve, ensuring the solenoid valve, pneumatic actuator, and alarm test loop ball valve are turned off.
- Q: How is water injection, pressurization, and standby readiness completed? Switch on the ball valve on the water injection loop and slowly press the reset valve button. Water flowing out of the drain hole during this process is normal and will stop once pressure in the diaphragm chamber increases. Release the button when the water supply pressure gauge and diaphragm chamber pressure gauge show identical readings, then completely open the front water supply control valve. Ensure the alarm system is open when the deluge valve group is in ready condition.
Contact Person: Ms. Cui
WeChat: cuiyuying01
Email: njcuishusheng@vip.163.com
Email: rain.cui@apc-valve.com
Tel.: +86 18600252968
Tel.: +86 534 5571078
Fax: +86-534-5216766
Relevant news
APC Industries
Mobile website
Add WeChat chat
CONTACT US
Add:No. 18 Taishan Road, Ningjin County, Shandong Province P.R.China
Mobile:+8618600252968
WeChat:cuiyuying01
E-Mail: